Pressure prove switch open, OR blocked inlet/exhaust vent, OR pressure switch closed before the combustion air inducer started.
§1Likely causes
- Blocked inlet or exhaust vent
- Pressure switch open
- Pressure switch closed prior to inducer activation
§2Safe DIY steps
- Check outdoor inlet/exhaust terminations for blockage
- Techniciancheck pressure switch and venting
§3When to call a pro
Call a licensed HVAC technician: if vents are clear and the code persists.
Find a local HVAC pro →§4Other Lennox codes
Improper main ground, OR line voltage below 90 volts. Control will not respond to a heat call until voltage rises above 95 volts.
Alternating slow flashLennoxWatchguard 1 hour: burners failed to ignite or lost flame 5 times during a single heating demand.
Board failure patternLennoxCircuit board failure or control wired incorrectly.
Red fast flash, green slow flashLennoxMain power polarity reversed. Switch line and neutral.
Red on, green slow flashLennoxRollout switch open, OR 12-pin connector improperly attached.
Red slow flash, green fast flashLennoxLow flame signal: measures below 1.5 microamps. Replace flame sense rod.