Ignition lockout: system failed to ignite gas and prove flame in 4 attempts. Control auto-resets after 3 hours (see code 34).
1Likely causes
- Oxide buildup on flame sensor
- Manual gas shut-off valve or gas valve turned off
- Low inlet gas pressure
- Defective hot surface igniter
- Inadequate flame carryover or rough ignition
- Control ground continuity problem
2Safe DIY steps
- Check that the manual gas shut-off valve is open and the gas valve control switch is ON
- Technicianclean flame sensor with fine steel wool and check flame current (0.5 microamp DC minimum, 4.0-6.0 nominal)
- Techniciancheck inlet gas pressure, igniter and ground (green/yellow wire must be connected to furnace sheet metal)
3When to call a pro
Call a licensed HVAC technician: if gas is on and the furnace still fails to light.